Hazardous Area Surge Protection Equipment For 4-20mA Measuring Control And Bus System

Hazardous Area Surge Protection Equipment For 4-20mA Measuring Control And Bus System

  • Hazardous Area Surge Protection Equipment For 4-20mA Measuring Control And Bus System
  • Hazardous Area Surge Protection Equipment For 4-20mA Measuring Control And Bus System
  • Hazardous Area Surge Protection Equipment For 4-20mA Measuring Control And Bus System
Hazardous Area Surge Protection Equipment For 4-20mA Measuring Control And Bus System
Product Details:
Place of Origin: Guangzhou
Brand Name: TSTLP
Certification: CE Compliance
Model Number: TS-EX24
Payment & Shipping Terms:
Minimum Order Quantity: Negotiable
Price: Negotiable if good quantity
Packaging Details: By standard export box/carton
Delivery Time: Around 7 working days upon receipt of payment
Payment Terms: 100% TT / LC / Western Union / MoneyGram / WeChat Transfer / Alipay / Wanda Money Transfer / Cash ahead
Supply Ability: 2000 sets/month
Contact Now
Detailed Product Description
Un: 24V Uc: 32V- / 22.5~
Iimp: 1.5kA IL: 0.55A
In: 10kA FG: 67MHz
Enclosure Material: Stainless Steel Case Compliance: IEC-61643-21 / GB18802.21 / YD/T 1542
High Light:

din rail surge protector

,

electrical surge protection devices

Hazardous area surge protection device for 4-20mA measuring control & bus system

 

Installed at LPZ OB-2 or higher inside the control equipment, the built-in cable connected with the control equipment’s wiring terminal. TS-24 hazardous area surge protection device is available to apply in intrinsically safe circuit in hazardous areas and 4-20mA measuring control system and bus system.

 

  • Technical Data of TS-EX24 Hazardous area surge protection equipment
Model Number   TS-EX24
Normal Voltage Un 24V-
Rated voltage (max. continuous voltage) Uc

32V-

22.6V ~

Lightning impulse current (10/350) Iimp 1.5kA
Normal current IL 0.55A
Nominal discharge current (8/20) In 10kA (per line); 10kA(total)
Voltage protection level at In Up ≤ 58V (line/line); ≤ 1700V (line/PG)
Voltage protection level at 1kV/μs Up ≤ 50V (line/line); ≤ 1200V (line/PG)
Bandwidth fG 67MHz
Capacitance C ≤ 25pF (line/line); ≤ 15pF (line/PG)
Operating temperature range   -40 0C ~ +80 0C
Mounting in   M20 x 1.5 screws
Connection (input / output)   1.3 mm x 250mm length of the connecting lead
Earthing via   Connecting lead
Enclosure material   Stainless steel case
Compliance   IEC-61643-21, GB18802.21, YD/T 1542

 

  • MAIN CHARACTER
  1. Small & easy replacement.
  2. Easy to install inside the control equipment.
  3. Stainless steel housing, fireproof & explosion-proof outdoor use.

 

Installation Instruction

  • Screwing into the wiring port of the control equipment directly
  • Blue wire connecteed with signal port “+”, Black Wire connected with signal port “-”
  • Yellow / Green wire connect with grounding port “GN” of grounding system.
  • After installation, check if commuication is be operating normally.

Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replace the SPD.

 

INSTALLATION DIAGRAM

Hazardous Area Surge Protection Equipment For 4-20mA Measuring Control And Bus System 0

 

 

WARNING:

  • The hazardous area surge protection device must be installed by electrically skilled person, conforming to national standards and safety regulations.
  • It is recommended that installation should be done under power off condition.

 

PDF Catalog Download - TS-EX24 SPD for Hazardous ...

 